Connect via RS-232 serial cable or USB-to-serial adapter (legacy systems use 9600 baud). Go to Online > Download. You have two options:
RULE 0001
WHEN ZONE(Z001) = ALARM
THEN TURNOUT CKT(1,1)
DELAY 10 SECONDS
TURNOUT CKT(1,2)
SEND MESSAGE "FIRE ON FLOOR 1"
The SDU includes a rule compiler that checks for circular references, overlapping conditions, and syntax errors before downloading. est3 sdu software
A technician using SDU in the field might: Connect via RS-232 serial cable or USB-to-serial adapter
Open the "SLC Database" spreadsheet. Enter loop 1, address 1: Model = SIGA-PS (Photo detector). Address 2: SIGA-CR (Control Relay). Use the "Fill Series" feature to populate hundreds of devices quickly. The SDU includes a rule compiler that checks